Model Number : HGDS1000

Certification : SILII CE

Place of Origin : China

MOQ : 1pc

Price : Negotiable according to configuration

Payment Terms : T/T, L/C, Western Union

Supply Ability : 500000 pcs per year

Delivery Time : 20-30 days

Packaging Details : carton

Name : GDS system of fixed gas detector

AC/DC power supply : Voltage: Rated AC100V ~ AC240V (root mean square), tolerance -15% ~ +10% (85VAC ~ 264VAC) Frequency: rated 50Hz or 60Hz, the tolerance -6% ~ +4% (47Hz ~ 63Hz)

Field power supply : 24V DC (-15% ~ +20%)

System power supply : 24V DC (-15% ~ +20%)

Operating ambient temperature : 0℃~60℃, EN60068-2-14, Test Nb

Storage temperature : -40 ℃ ~ +70 ℃, EN60068-2-14, Test Na

Relative humidity : 5%~95%, no condensation, EN60068-2-30, Test Db

Ingress protection : IP66

solation withstand voltage (field to the system) : 500V AC test 1min., leak current no greater than 5mA

SIL : SIL2

IP protection class : IEC60529 IP20 (preventing the entry of external things of size over 12 mm, non-watertight)

Electrical Safety : EC 61131-2,IEC 61010-1,IEC 61010-2-201. Enclosed, SELV/PELV circuits.

Brand Name : WG Sensor™

OEM/ODM : Supported

E-Mail : sales@wgsensor.com

WhatsApp : +8613333637163

Contact Now

TUV certified SIL II GDS gas detection system of Fixed Gas Detectors for industrial application

Product Brief Introduction:
HGDS1000 safety control system meets the requirements of system capability of safety integrity level SIL2 with large capacity, high availability, superior performance, fast response characteristics, can be widely used in petrochemical, fine chemical industry, oil and gas pipeline transmission, hospital safety equipment and enterprise ESD system. Control system are composed of controller and the IO module to complete the functions of data acquisition, logic operation, action output, human-computer interaction and so on, so as to realize the security protection function.
Features:

High Availability

(1) Adopt dual rack redundant structure, including power redundancy, controller redundancy and network redundancy.
(2) In redundancy mode, the system can still run when there is a single fault.
Fast Response
(1) The typical time of redundancy switching is 90 ms.
(2) The minimum time of task scheduling is less than100 us.
(3) The fastest control cycle of loop is 50 ms.
Large Capacity
(1) Single-DP network, 124 IO slaves can be added.
(2) The IO capacity supported by the system is more than 10,000 points.
Easy Maintenance
(1) More than 10,000 logs are recorded by logging tools, including abnormal operations, faults and other information.
(2) Module information and diagnostic information of each module can be obtained respectively through Module Information Instruction Library and System State Instruction Library.
(3) Each module is hot-swappable.
(4) Update the system by SD card or HGDS-AutoThink software.

Technical parameters:

Reliability specifications

AC/DC power supply

Voltage: rated AC100V ~ AC240V (root mean square value), tolerance -15% ~ +10% (85VAC ~ 264VAC)
Frequency: rated 50Hz or 60Hz, tolerance-6%~+4%(47Hz~63Hz)

Power supply on Site 24V DC (-15% ~ +20%)
System Power Supply 24V DC (-15% ~ +20%)
Working Environment Temperature 0℃~60℃, EN60068-2-14, Test Nb
Storage Environment Temperature -40 ℃ ~ +70 ℃, EN60068-2-14, Test Na
Humidity 5%~95%, no condensation, EN60068-2-30, Test Db
Working Altitude ≤2000m
Storage Altitude ≤3000m
Electrical Safety Meet the requirement of IEC 61131-2, IEC 61010-1, IEC 61010-2-201. Enclosed, SELV/PELV circuits.
Isolation withstand voltage (field to system) 500V ACt1mistn,leakage current is not more than 5mA
Over voltage level II
IP protection grade IEC60529 IP20(the foreign matter more than 12mm can not enter,not waterproof)
Pollution Level 2
Vibration Sinusoidal vibration (durability) 0.5G @ 10 to 150Hz, 3 axis, 20 times per axis, IEC 60068-2-6
Sinusoidal vibration (operation) 3.5mm @ 5 to 8.4Hz, 3 axis, 10 times per axis, IEC 60068-2-6
1G @ 8.4 to 150Hz, 3 axis, 10 times per axis, IEC 60068-2-6
shock Half sinusoidal, 15G peak for 11ms, 3 axis, 18 times in total, IEC 60068-2-27
collision (0.5±0.04)J, 3 times per spot
EMC Radiation emission IEC 61131-2, EN 61000-6-4, EN 50121-4
Conducted emission IEC 61131-2, EN 61000-6-4, EN 50121-4
Electrostatic discharge IEC 61000-4-2 Contact discharge ±6 kV, Air discharge ±8 kV.
Radio frequency electromagnetic field radiation immunity

IEC61000-4-3
80MHz~1000MHz, 20V/m
1.4GHz~2.0GHz, 10V/m
2.0GHz~6GHz, 5V/m
80 % AM (1 kHz)

Power frequency magnetic field immunity IEC 61000-4-8 100 A/m (50 Hz)
Electrical fast transient burst

AC power port:
2kV (5/50 ns, 5 kHz and 100 kHz)
4kV (5/50 ns, 5 kHz and 100 kHz)

Signal port:
2kV (5/50 ns, 5 kHz and 100 kHz)
2kV (5/50 ns, 5 kHz and 100 kHz), DIO with shielded lines

surge

AC power port:
2kV CM, 1kV DM
4kV CM, 2kV DM

Signal port:
2kV CM

RF conducted immunity

IEC61000-4-6
20V, 150 kHz to 80 MHz
80%AM(1kHz)

0Hz~150kHz Common mode conduction immunity

AC power port:
1 V to 10 V increasing with 20 dB/decade (1,5 kHz to 15 kHz).
10 V (15 kHz to 150 kHz)

Signal port:
1 V to 10 V increasing with 20 dB/decade (1,5 kHz to 15 kHz);
10 V (15 kHz to 150 kHz)
10 V (continuous: DC, 16 2/3 Hz, 50 Hz, 150 Hz)
100 V (short duration 1 s: DC, 16 2/3 Hz, 50 Hz)

Voltage dips, short interruptions

0 % during 0.5 cycle
0 % during 1 cycle

40 % during 10 cycles
70 % during 25 cycles
0 % during 250 cycles

TUV certificate:

Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V

Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V

Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V

Company profile:

Henan Weiguo Intelligent Technology Co., LTD., founded in 2015, is an important subsidiary of Hanwei Electronics Group Corporation (Stock no.:300007) in the field of intelligent healthy, safe home and IoT business. Henan Weiguo Intelligent Technology Co., LTD., relying on the core sensor technology, focuses on gas and smoke alarm, air quality monitor, alcohol tester and firefighting products. Based on introduction of featured technology from both Hanwei Electronics Group Corporation and abroad, Henan Weiguo intelligent Technology Co., LTD., has developed into an innovative company with the collection of design, R&D development, production, sales and service. We will always be committed to becoming the leader in intelligent hardware, providing safe, healthy, environmentally friendly and intelligent working and living environment for families and users all over the world.

(Hanwei Electronics Group Corporation (Stock no.:300007), founded in 1998, is an influential manufacturer of gas sensors and instruments in China and a leading supplier of sensor-based IoT solutions in China. Hanwei Electronics Group Corporation is committed to providing perfect solutions for smart city, safe production, environmental protection and people's health.)
Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V
Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V


Product Tags:

GDS Fixed Gas Detector AC240V

      

Fixed Gas Detector AC100V

      

TUV SIL II GDS Gas Detector

      
Quality Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V for sale

Large Capacity TUV SIL II GDS Fixed Gas Detector AC100V AC240V Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Henan Weiguo Intelligent Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0